Setting Values
STEP NO. DESCRIPTION
FACTORY SETTING
Slimline 150
ADJUSTING RANGE
STEP
1
Air flow rate mode /
30 m
3
/h
0 m
3
/h of 30 m
3
/h
2
Air flow rate mode 1 /
75 m
3
/h
30 m
3
/h t/m 300 m
3
/h
5 m
3
/h
3
Air flow rate mode 2 /
100 m
3
/h
30 m
3
/h t/m 300 m
3
/h
5 m
3
/h
4
Air flow rate mode 3 /
125 m
3
/h
30 m
3
/h t/m 300 m
3
/h
5 m
3
/h
5
Bypass temperature
22,0 °C
15,0 °C - 35,0 °C
0,5 °C
6
Bypass hysterese
2,0 °C
0,0 °C - 5,0 °C
0,5 °C
7
Operation bypass valve
0
0 (= Automatic)
1 (= Bypass valve closed)
2 (= Bypass valve open)
8
Central h
heat recovery
OFF
OFF (=Central heat recovery off)
ON (= Central heat recovery on)
9
Imbalance permissible
ON
OFF (= flow rate supply equals extract)
ON (= imbalance permissible)
10
Fixed imbalance
0 m
3
/h
-100 m
3
/h t/m 100 m
3
/h
1 m
3
/h
STEP NO. DESCRIPTION
FACTORY SETTING
Slimline 150 Plus
ADJUSTING RANGE
STEP
11
Heater
0
0 (= no additional heater)
1 (= additional preheater)
2 (= postheater)
12
Temperature postheater
21,0 °C
15,0 °C t/m 30,0 °C
0,5 °C
13
Selection input 1
0
0 (= normally open contact)
1 (= 0 - 10V input active)
2 (= normally closed contact)
3 (= input 1/ bypas open
→
12V;
bypass closed
→
0V)
4 (= input 1/ bypas open
→
0V;
bypass closed
→
12V)
14
Minimum voltage input 1
0,0 V
0 Volt - 10 Volt
0,5 V
15
Maximum voltage input 1
10,0 V
0 Volt - 10 Volt
0,5 V
16
Conditions
switching input 1
0
0 (off)
1 (on)
2 (= On if conditions bypass open satisfied)
3 (= Bypass control)
4 (= Bedroom valve)
17
Supply fan mode
switching input 1
5
0 (= Input fan off)
1 (= Absolute min. flow rate 30m
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6 (= Maximum flow rate)
7 (= No input fan activation)