Initial Installation
QUALIFIED INSTALLERS ONLY
i
nstaLLing
the
u
nit
:
• Remove the packaging from the appliance and check to make sure there is no damage. Carefully check
the glass door. Do not use the unit if it is damaged. In the event damage is found, please report it to
your dealer as soon as possible.
• Carefully clean the fireplace and flue before installing the stove. Failure to do so may result in fumes
or soot being blown into the room and may cause a fire leading to death or serious injury.
instaLLation instRuctions:
2ft (0.6m)
Minimum
3ft (0.9m)
Minimum
Within
10ft (3m)
Roof ridge or
any other portion
of a building
1. Plan your installation and clearances to
combustibles. The E33 may be installed
and vented into any solid fuel fireplace
that has been installed in accordance
with the National, Provincial/State
and local building codes and has
been constructed of non-combustible
materials. Also refer to the Also refer
C
learanCes
to
C
ombustIbles
section.
2.
Remove door. See
m
aIntenanCe
anD
s
erVICe
- g
lass
D
oor
r
emoVal
.
3. Remove wrapping material and check for any damage. If damage is observed, do not use unit and
contact your local dealer.
4. Check that the chimney clean outs fit properly. The flue damper must be fully blocked open or removed
for installation of the E33; the smoke shelves, shields and baffles may be removed if attached by
mechanical fasteners.
Table 5: Vent termination clearances
Minimum Clearance*
Description
3 ft (0.9 m)
Clearance above the highest point where it passes through a roof surface, refer to
Figure 29.
24 in (0.6 m)
Clearance above a roof ridge, any other portion of a building, or any other obstruc-
tion within a horizontal distance of 10 feet (3 m), refer to Figure 29.
5 ft (1.5 m)
Clearance for a vent or chimney above either the highest connected appliance
drafthood outlet, or flue collar.
6 ft (1.83 m)
Clearance to mechanical air supply inlet.
3ft (0.9m)
Clearance to each side of center line extended above meter/regulator assembly.
6 ft (1.83 m)
Radial clearance around service regulator vent outlet.
12 in (30 cm)
Clearance above grade, verandah, porch, deck, or balcony.
3 ft (0.9 m)
Clearance to a building opening or combustion air inlet of another appliance, ex-
cept with the approval of the authority having jurisdiction for the following reduced
clearances.
9 in (0.23 m)
Exception for inputs up to and including 50,000 Btu/h (15kW)
12 in (0.3 m)
Exception for inputs exceeding 50,000 Btu/h (15kW) but not exceeding 100,000
Btu/h (30kW)
*Clearances are in accordance with local installation codes and the requiremenets of the gas supplier
Figure 31: Roof Clearances.