Commissioning
Smartec CLD18
26
Hauser
8.3
Configuring the measuring device
1. Use the 'E' key to call up the main menu.
2. Navigate through the available menus with the '+' and '–' keys.
3. Press the 'E' key to open the desired menu.
4. Use the option,
Back
which can be found at the bottom of each menu, to move up a
level in the menu structure.
Default settings are in bold.
Parameter
Possible settings
Description
Current range
4-20 mA
0-20 mA
‣
Select the current range.
Out1 0/4 mA
0 to 2000000 μS/cm
0 μS/cm
‣
Enter the measured value at which the min. current value (0/4 mA) is
present at the transmitter output.
Out1 20 mA
0 to 2000000 μS/cm
0 μS/cm
‣
Enter the measured value at which the max. current value (20 mA) is
present at the transmitter output.
Out2 0/4 mA
-50 to 250 °C
0.0 °C
‣
Enter the measured value at which the min. current value (0/4 mA) is
present at the transmitter output.
Out2 20 mA
-50 to 250 °C
100.0 °C
‣
Enter the measured value at which the max. current value (20 mA) is
present at the transmitter output.
Damping main 0 ... 60 s
0 s
Damping value for the conductivity measured value
Extended setup
Advanced settings→ 26
Manual hold
Off
,
On
Function for freezing the current and alarm outputs
8.4
Advanced settings
1. Use the 'E' key to call up the main menu.
2. Navigate through the available menus with the '+' and '–' keys.
3. Press the 'E' key to open the desired menu.
4. Use the option,
Back
which can be found at the bottom of each menu, to move up a
level in the menu structure.
Default settings are in bold.
Parameter
Possible settings
Description
System
General settings
Device tag
Customized text
Max. 16 characters
Enter the device designation