Commissioning
Proservo NMS80
62
Hauser
7.5.3
Configuration of a connected RTD
D
E
F
C
B
A
1
1
1
1
3
2
2
4
1
HR
CDI
WP
on
SIM
2
2
3
3
4
4
1 2 3
4 5 6 7 8
POWER
i
1 2 3
4 5 6 7 8
B
B1-3
B4-8
1 2 3
4 5 6 7 8
C
1 2 3
4 5 6 7 8
C1-3
C4-8
A0032465
32
Possible locations of the Analog I/O modules, to which an RTD can be connected. The order code
of the device determines which of these modules is actually present.
Submenu: Setup → Advanced setup → Input/output → Analog IP
Parameter
Meaning / Action
RTD type
Specify the type of the connected RTD.
RTD connection type
Specify the type of connection of the RTD (2-, 3- or 4-wire).
Input value
Check whether the indicated value matches the actual temperature.
Minimum probe temperature
Specify the minimum approved temperature of the connected RTD.
Maximum probe temperature
Specify the maximum approved temperature of the connected RTD.
Probe position
Enter the mounting position of the RTD (measured from the datum plate).