Proservo NMS80
Commissioning
Hauser
69
Each Analog I/O module of the device can be configured as 4...20mA analog output. To do so,
assign appropriate values to the following parameters:
Setup → Advanced setup → Input/output → Analog I/O
Parameter
Meaning / Action
Operating mode
Select
4..20mA output
or
HART slave +4..20mA output
Analog input source
Select which tank variable is transmitted via the analog output.
Analog input 0% value
Specify which value of the tank variable corresponds to an output current of 4 mA.
Analog input 100% value
Specify which value of the tank variable corresponds to an output current of 20 mA.
1)
"HART slave +4..20mA output " means that the Analog I/O module serves as a HART slave which cyclically sends
up to four HART variables to a HART master. For the configuration of the HART output: