Installation
6.1
Installation conditions
For mechanical reasons and to protect the pipe, support is recommended for heavy sensors
(e.g. with a hot-tap retractable assembly).
6.1.1
Mounting position
Orientation
The direction of the arrow on the sensor body helps you to install the sensor according to the
flow direction (direction of medium flow through the piping).
For detailed information on aligning with the flow direction: (→ 19)
Installation is generally not recommended in the event of high vibrations or unstable
internal fittings.
Orientation
Recommendation
Vertical orientation
A0017337
Horizontal orientation, transmitter head up
A0015589
Horizontal orientation, transmitter head
down
A0015590
1)
Partially filled pipe detection is not possible in this orientation.
For detailed information about partially filled pipe detection, refer to the Operating
Instructions for the device on the CD-ROM provided
Pipes
The measuring device must be professionally installed, and the following points must be
observed: