Installation
Proline t-mass T 150
20
Hauser
20 × DN
5 × DN
5 × DN
35 × DN
35 × DN
5 × DN
5 × DN
5 × DN
35 × DN
5 × DN
50 × DN
20 × DN
1
4
2
6
3
5
A0022381
1
reduction
2
expansion
3
90 ° elbow or T-section
4
2 × 90° elbow
5
Control valve
6
2 × 90 ° elbow 3-dimensional
6.1.2
Requirements from environment and process
Ambient temperature range
Measuring device
–40 to +60 °C (–40 to +140 °F)
Local display
–20 to +60 °C (–4 to +140 °F), the readability of the display may be impaired at
temperatures outside the temperature range.
‣
If operating outdoors:
Avoid direct sunlight, particularly in warm climatic regions.
System pressure
NOTICE
Depending on version:
Observe information on nameplate.
‣
Max. 40 bar g (580 psi g)
!
WARNING
If the coupling is opened incorrectly under full process pressure, the sensor will shoot
out. Therefore it must be ensured that the sensor does not accelerate to a dangerous exit
velocity.
‣
Use a safety chain for pressures > 4.5 bar (65.27 psi) in combination with PEEK clamping
ferrules .