Proline t-mass T 150
Electrical connection
Hauser
27
Order code
for
"Output,
input"
Terminal numbers
Output 1
Output 2
Input
26 (+)
27 (-)
24 (+)
25 (-)
22 (+)
23 (-)
Option
K
-
Pulse/frequency/switch output
(passive)
-
Option
Q
4-20 mA HART (active)
Pulse/frequency/switch output
(passive)
Status input
1)
Securely tighten the screws of the terminal. Recommended torque: 0.5 Nm.
7.1.4
Pin assignment of the connector
Supply voltage
Supply voltage for all communication types (on the device side)
1
2
4
3
5
A0016809
Pin
Assignment
Coding
Plug/socket
1
L+
DC24 V
A
Plug
2
+
Status input
3
-
Status input
4
L-
DC24 V
5
Grounding/shielding
4-20 mA HART with pulse/frequency/switch output
4-20 mA HART with pulse/frequency/switch output (on the device side)
3
2
4
1
5
A0016810
Pin
Assignment
Coding
Plug/socket
1
+
4-20 mA HART (active)
A
Socket
2
-
4-20 mA HART (active)
3
+ Pulse/frequency/switch output (passive)
4
-
Pulse/frequency/switch output (passive)
5
Grounding/shielding
7.1.5
Requirements for the supply unit
Supply voltage
DC 24 V (18 to 30 V)
The power supply circuit must comply with SELV/PELV requirements.