Electrical connection
Proline Promag L 800
34
Hauser
7.2.3 Connecting the connecting cable in the remote version
1.
Open the housing cover.
– Release the four screws with a Phillips head screwdriver.
– Lift the housing cover slightly and tip it to the left.
Two flexible fasteners secure the housing cover to the housing.
2.
Push the cable through the cable entry
To ensure tight sealing, do not remove the sealing ring from the cable entry.
3.
Strip the cable ends and fit wire end ferrules
28.
4.
Connect the cables in accordance with the terminal assignment. When connecting the
cable shield to the ground terminal, observe the grounding concept of the facility.
A0017027
Fig. 21: Connecting the remote version
1
Transmitter terminals
2
Sensor terminals
3
Coil current cable
4
Electrode cable
5.
Fit the cable anchorage, firmly tighten the cable glands and secure the housing cover
again.
1
2
3
4
17
16
15
14
10
9
8
7
6
5
13
12
11
4
3
2
1
5
7
4
37
42
41
Sensor
Transmitter
Terminal
Connection
Terminal
Connection
5
Electrode E1 (brown)
1
Electrode E1 (brown)
7
Electrode E2 (white)
2
Electrode E2 (white)
4
Reference electrode,
Terminals bridged (green)
3
Shield, electrode E1 (brown)
37
4
Shield, electrode E2 (white)
41
Coil current cable B2 (black)
11
Reference electrode (green)
42
Coil current cable B1 (black)
12
Coil current cable B2 (black)
13
Coil current cable B1 (black)
Содержание Proline Promag L 800