Device functions - electromagnetic measuring systems
Proline Fieldcheck
50
Hauser
10.1.1
Group SIMULATION
Function group CONFIGURATION
Function description
FUNCTION
SIMULATION
CONFIGURATION
OPERATION MODE
Use this function to select the operation mode for the simulation.
There are two freely adjustable flow signals of –12.5 m/s to +12.5 m/s and the assigned
duration of simulation is 1 second to 999 seconds.
Options:
CONTINUOUS
The flow behavior in the process has low dynamics.
a0001708
Q1 = Simulation value 1
STEP
The flow rates in the process are very dynamic and change very quickly. This operation
mode is also suitable for the simulation of flows outside the tolerance limits (fault
simulation). Here very dynamic or disrupted conditions can also be simulated.
a0001709
Q1 = Simulation value 1, Q2 = Simulation value 2, T1 = Duration of simulation 1, T2
= Duration of simulation 2
PROFILE
For the depiction of real sequences in the course of a process or of a filling procedure.
The controlled rise or fall from one flow value to the next can be depicted.
a0001710
Q1 = Simulation value 1, Q2 = Simulation value 2, T1 = Duration of simulation 1,
T2 = Duration of simulation 2, T3 = Profile time 1, T4 = Profile time 2
Factory setting:
CONTINUOUS
Q
Q1
START
STOP
t
Q
Q1
Q2
T2
T1
START
STOP t
Q
Q2
Q1
T2
T3
T4
T1
START
STOP