Diagnostics and troubleshooting
Micropilot FMR51, FMR52 HART
80
Hauser
12.5 Overview of diagnostic events
Diagnostic
number
Short text
Remedy instructions
Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
Diagnostic of electronic
242
Software incompatible
1. Check software
2. Flash or change main
electronics module
F
Alarm
252
Modules incompatible
1. Check electronic modules
2. Change I/O or main electronic
module
F
Alarm
261
Electronic modules
1. Restart device
2. Check electronic modules
3. Change I/O Modul or main
electronics
F
Alarm
262
Module connection
1. Check module connections
2. Change electronic modules
F
Alarm
270
Main electronic failure
Change main electronic module
F
Alarm
271
Main electronic failure
1. Restart device
2. Change main electronic module
F
Alarm
272
Main electronic failure
1. Restart device
2. Contact service
F
Alarm
273
Main electronic failure
1. Emergency operation via display
2. Change main electronics
F
Alarm
275
I/O module defective
Change I/O module
F
Alarm
276
I/O module faulty
1. Restart device
2. Change I/O module
F
Alarm
276
I/O module failure
F
Alarm
282
Data storage
1. Restart device
2. Contact service
F
Alarm
283
Memory content
1. Transfer data or reset device
2. Contact service
F
Alarm
311
Electronic failure
Maintenance required!
1. Do not perform reset
2. Contact service
M
Warning
Diagnostic of configuration
410
Data transfer
1. Check connection
2. Retry data transfer
F
Alarm
411
Up-/download active
Up-/download active, please wait
C
Warning
412
Processing download
Download active, please wait
C
Warning
431
Trim 1 to 2
Carry out trim
C
Warning
435
Linearization
Check linearization table
F
Alarm
437
Configuration
incompatible
1. Restart device
2. Contact service
F
Alarm
438
Dataset
1. Check data set file
2. Check device configuration
3. Up- and download new
configuration
M
Warning
441
Current output 1 to 2
1. Check process
2. Check current output settings
S
Warning
484
Failure mode simulation Deactivate simulation
C
Alarm
Содержание Micropilot FMR50