Commissioning via operating menu
Micropilot FMR51, FMR52 HART
68
Hauser
11.3 Configuration of a level measurement
F
L
D
E
100%
0%
R
A0016933
21
Configuration parameters for level measurements in liquids
R
Reference point of the measurement
D
Distance
L
Level
E
Empty calibration (= zero)
F
Full calibration (= span)
1. Navigate to: Setup → Device tag
Enter device tag.
2. Navigate to: Setup → Distance unit
Select distance unit.
3. Navigate to: Setup → Tank type
Select tank type.
4. For
Tank type
parameter = Bypass / pipe:
Navigate to: Setup → Tube diameter
Enter the diameter of the stilling well or bypass.
5. Navigate to: Setup → Medium group
Specify medium group: (
Water based (DC >= 4)
or
Others
)
6. Navigate to: Setup → Empty calibration
Enter empty distance E (Distance from reference point R to the 0% level)
7. Navigate to: Setup → Full calibration
Enter full distance F (Distance from the 0% to the 100% level).
8. Navigate to: Setup → Level
Indicates the measrued level L.
9. Navigate to: Setup → Distance
Indicates the measured distance from the reference point R to the level L.
10. Navigate to: Setup → Signal quality
Indicates the quality of the evaluated level echo.
5)
If, for example, the measuring range covers only an upper part of the tank (E << tank height), it is mandatory to enter the acutal tank height into
the "Setup → Advanced Setup → Level → Tank/silo height" parameter.
Содержание Micropilot FMR50
Страница 116: ...Operating menu Micropilot FMR51 FMR52 HART 116 Endress Hauser User interface Init recording In progress Finished ...
Страница 183: ......
Страница 184: ...www addresses endress com 71344017 71344017 ...