Levelflex M FMP43 with PROFIBUS PA
Commissioning
Hauser
63
Display (008)
The
distance
measured from the reference point to the product surface and the
meas. value
calculated with the aid of empty calibration are displayed. Check whether the values correspond to
the actual measured value or the actual distance. The following cases can occur:
• Distance correct – meas. value correct -> continue with the next function
"
check distance
"
(051)
.
• Distance correct – meas. value incorrect -> Check "
empty calibr.
"
(005)
• Distance incorrect – meas. value incorrect -> continue with the next function
"
check distance
"
(051)
.
Function "check distance" (051)
This function triggers the mapping of interference echoes. To do so, the measured distance must be
compared with the actual distance to the product surface. The following options are available:
Options:
• Distance = ok
• Dist. too small
• Dist. too big
• Dist. unknown
•
Manual
• Probe free
L00-FMP4xxxx-14-00-06-en-010
Distance = ok
Use this function for partially covered probes. Choose "
manual
" or "
probe free
" if the probe is free.
• Mapping is carried out up to the currently measured echo
• The range to be suppressed is suggested in the "
range of mapping
"
(052)
function
It is wise to carry out a mapping even in this instance.
⇒
E HAUSER
E
+
–
⇒
E HAUSER
E
+
–
+
+
distance too small
distance = ok
Содержание Levelflex M FMP43
Страница 4: ...Brief overview Levelflex M FMP43 with PROFIBUS PA 4 Endress Hauser...
Страница 104: ...Appendix Levelflex M FMP43 with PROFIBUS PA 104 Endress Hauser...
Страница 106: ...Levelflex M FMP43 with PROFIBUS PA Index 106 Endress Hauser...
Страница 108: ...www endress com worldwide BA358F 00 en 07 07 No 71041163 CCS FM SGML 6 0 ProMoDo 71041163...