Levelflex M FMP43 with PROFIBUS PA
Commissioning
Hauser
75
6.8.1
Envelope curve with the ToF Tool
After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope
curve (
75).
L00-FMP4xxxx-20-00-00-en-007
!
Note!
In the event of severe interference echoes, installing the Levelflex at another point can optimize the
measurement routine.
Evaluating the measurement with the aid of the envelope curve
Typical curve shapes:
The following examples display typical curve shapes for a rope or rod probe in an empty tank. For
all probe types, a negative probe end signal is shown. For rope probes, the end weight causes an
additional preliminary positive echo (see rope probe diagram).
L00-FMP40xxx-05-00-00-en-024
Level echoes are indicated as positive signals in the envelope curve. Interference echoes can be both
positive (e.g. reflections from internals) and negative (e.g. nozzles). The envelope curve, the map
and the differential curve are used for the evaluation. Level echoes are searched for in the
differential curve.
400.00
400.00
[mV]
[mV]
300.00
300.00
200.00
200.00
100.00
100.00
0.00
0.00
-100.00
-100.00
-200.00
-200.00
-300.00
-300.00
-400.00
-400.00
-500.00
-500.00
0.00
0.00
0.20
0.20
0.40
0.40
0.60
0.60
0.80
0.80
1.00
1.00
1.20
1.40
[m]
[m]
LN
LN
E
E
F
F
(1.00 m, -143.00 mV)
(1.08 m, -115.00 mV)
Rod probe
Rope probe
Probe end signal
Launch pulse
Probe end signal
Launch pulse
Содержание Levelflex M FMP43
Страница 4: ...Brief overview Levelflex M FMP43 with PROFIBUS PA 4 Endress Hauser...
Страница 104: ...Appendix Levelflex M FMP43 with PROFIBUS PA 104 Endress Hauser...
Страница 106: ...Levelflex M FMP43 with PROFIBUS PA Index 106 Endress Hauser...
Страница 108: ...www endress com worldwide BA358F 00 en 07 07 No 71041163 CCS FM SGML 6 0 ProMoDo 71041163...