Levelflex M FMP43 with PROFIBUS PA
Commissioning
Hauser
65
The distance measured from the reference point to the product surface and the measured value
calculated with the aid of the empty calibration are displayed again. Check whether the values
correspond to the actual meas. value or the actual distance. The following cases can occur:
• Distance correct – meas. value correct -> basic setup completed
• Distance incorrect – meas. value incorrect -> another interference echo suppression must be
carried out "
check distance
"
(051)
.
• Distance correct – meas. value incorrect -> check "
empty calibr
"
(005)
!
Note!
After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope
curve ("
envelope curve
"
(0E)
function group) (
75).
⇒
⇓
After 3 s, the following message appears
E HAUSER
E
+
–