Commissioning
Gammapilot M FMG60 FOUNDATION Fieldbus
62
Hauser
Further options:
• Level measurement (continuous)
• Point level detection
• Density measurement (with temperature compensation if required)
• Concentration measurement (density measurement followed by linearization)
The operating mode can only be selected once. After this, the function is
automatically locked and can only be unlocked by resetting the Gammapilot M ("Reset"
(*A3) function).
r
A
B
C
D
E
A0018108
A
Level measurement (continuous)
B
Point level detection
C
Density measurement (with temperature compensation if required)
D
Concentration measurement (density measurement followed by linearization)
ρ
Density
E
Concentration
7.3.6
"Density unit" (*06)
Local display
Density unit *06
✓
g/cm
3
g/l
lb/gal
This function is needed for density and concentration measurements only. It is used to
select the density unit.
Further options:
• g/cm
3
• g/l
• lb/gal; [1g/cm
3
= 8,345 lb/gal]
• lb/ft
3
; [1g/cm
3
= 62,428 lb/ft
3
]
• °Brix; [1°Brix =270 (1 - 1/x)]