Gammapilot M FMG60 FOUNDATION Fieldbus
Operation
Hauser
51
L_TYPE
XD_SCALE
SIMULATE
CHANNEL
DIRECT
INDIRECT
INDIRECT
SQRT
OUT_SCALE
ALARMS
OUT
HI_HI
HI
LO
LO_LO
0
EU
0
0
1
1
1
0
1
0
1
FIELD_VAL
EU
EU
EU
t
PV_TIME
MODE
STATUS
0
1
0
1
PROCESS VALUE (PV)
Transducer Block
PRIMARY / SECONDARY VALUE
A0018675
Operation
The Analog Input block is opened by clicking the "Analog_Input" line. Parameter changes
using the tool are made offline. The device can remain in operation during this time.
The changes are downloaded to the device by first setting MODE_BLK = OOS and then
pressing the WRITE CHANGES button. If you want to check all the values saved in the
device, click READ ALL. To return to operation, set the MODE_BLK to AUTO.
Block administration parameters
Parameter
Description
MODE_BLK
See the description under Resource block. The possible operating modes of the Transducer
block are:
• AUTO: the block is operating as normal
• MAN: the block is being operated with a manually entered main value
• OOS: the block is out of service
TAG_DESC
User description of the intended application of the block
BLOCK_ERROR Shows the error status in conjunction with the block components
• Out-of-Service: the block is in the OOS mode
• Simulation active: shows the setting of the SIM DIP switch. Input error/process variable with
BAD status
• Configuration error
Output values
Parameter
Description
PV
Either the primary/secondary output value of the Transducer block or a value associated with
it. Comprises the value and status.
OUT
The primary value output as a result of executing the Analog Input block. Comprises the value
and status.
FIELD_VALUE Raw value of the field device in % of PV range with a status reflecting the condition of the
transmitter: before signal characterization (L_type) or filtering (PV_TIME). Comprises the
value and status.
5)
If it is not possible to set MODE_BLK to AUTO, an error has occurred. Should this happen, check all the parameters, make the necessary changes
and try to set MODE_BLK to AUTO again