Installation
Gammapilot M FMG60 FOUNDATION Fieldbus
22
Hauser
Measurement of mass flow
Bulk solids applications on conveyor belts and conveyor screws.
The source container is positioned above the conveyor belt and the Gammapilot M FMG60
below the conveyor belt. The radiation is attenuated by the medium on the conveyor belt.
The intensity of the radiation received is proportional to the density of the medium. The
mass flow is calculated from the belt speed and the radiation intensity.
1
A0036637
1
Gammapilot M
4.3
Water cooling
The following applies for the versions of the Gammapilot M with a water cooling jacket:
• Material: 316L
• Water connection: 2 x G 1/4", DIN ISO 228
• Inlet temperature: max. 40 °C (104 °F)
• Outlet temperature: max. 50 °C (122 °F)(temperature monitoring recommended)
• Water pressure: 4 to 6 bar (60 to 90 psi)
A
B
G1/4"
G1/4"
*
A0018078
A
T <75 °C (167 °F)
B
T < 120 °C (248 °F)
L
CAUTION
The detector or cooling jacket can become damaged if the cooling water freezes.
‣
Empty the cooling jacket or protect against freezing.
L
WARNING
Pressurized water cooling system!
‣
Do not open the cylinder screws (see diagram below) when pressurized.