Commissioning
Deltapilot S FMB70
18
Hauser
• Position adjustment (zero point correction)
• Assignment of the lower and upper pressure value to the lower or upper level value
• Device reset
• The
and
keys only have a function in the following cases (for other settings, no
function is assigned to the keys.):
• LEVEL SELECTION "Level easy pressure", CALIBRATION MODE "Wet"
• LEVEL SELECTION "Level standard", LEVEL MODE "Linear", CALIBRATION MODE "Wet"
• The device is configured for the "Level" measuring mode as standard. You can change the
measuring mode by means of the MEASURING MODE parameter. See Operating
Instructions.
The following parameters are set to the following values at the factory. These parameters
can be changed only via the local display or remote operation, such as FieldCare.
• LEVEL SELECTION: Level easy pressure
• CALIBRATION MODE: Wet
• OUTPUT UNIT or LIN. MEASURAND: %
• EMPTY CALIB.: 0.0
• FULL CALIB.: 100.0.
• SET LRV: 0.0 (corresponds to 4 mA value)
• SET URV: 100.0 (corresponds to 20 mA value) SET URV: 100.0 (corresponds to 20 mA
value)
• Operation must be unlocked.
• The pressure applied must be within the nominal pressure limits of the sensor. See
information on the nameplate.
• LEVEL SELECTION, CALIBRATION MODE, LEVEL MODE, EMPTY CALIB., FULL CALIB., SET
LRV and SET URV are parameter names that are used for the local display or remote
operation, such as FieldCare.
L
WARNING
Changing the measuring mode can affect the calibration data!
This can result in product overflow.
‣
Check the calibration data if the measuring mode is changed.
Carrying out position adjustment
1. Make sure that pressure is present at the device. In doing so, pay attention to the
nominal pressure limits of the sensor.
2. Press the
key for at least 3 s.
LED on the electronic insert is lit briefly.
The applied pressure for position adjustment has been accepted.
Setting the lower range value
1. Make sure the desired pressure for the lower range value is present at the device. In
doing so, pay attention to the nominal pressure limits of the sensor.
2. Press the
key for at least 3 s.
LED on the electronic insert is lit briefly.
The applied pressure for position adjustment has been accepted.