Deltapilot S FMB70
Commissioning
Hauser
19
Setting the upper range value
1. Make sure the desired pressure for the upper range value is present at the device. In
doing so, pay attention to the nominal pressure limits of the sensor.
2. Press the
key for at least 3 s.
LED on the electronic insert is lit briefly.
The applied pressure for position adjustment has been accepted.
8.3.2
"Pressure measurement" measuring mode
See Operating Instructions.
• A Quick Setup menu is available for both the "Pressure" and "Level" measuring modes and
guides you through the most important basic functions. You specify which Quick Setup
menu should be displayed with the setting in the MEASURING MODE parameter.
• For a detailed parameter description, see the Operating Instructions BA00274P "Cerabar S/
Deltabar S/Deltapilot S, Description of Device Functions"
• Table 6, POSITION ADJUST.
• Table 7, BASIC SETUP
• Table 15, EXTENDED SETUP
• For pressure measurement, select the "Pressure" option via the MEASURING MODE
parameter. The operating menu is then structured according to the measuring mode that is
selected.
L
WARNING
Changing the measuring mode can affect the calibration data!
This can result in product overflow.
‣
Check the calibration data if the measuring mode is changed.