Deltapilot S FMB70
Commissioning
Hauser
17
Meaning
and
Copy the configuration data from the optional HistoROM®/M-DAT module
to the device.
and
Copy the configuration data from the device to the optional HistoROM®/M-
DAT module.
1
2
τ
on
off
• DIP switch 1: to lock/unlock parameters relevant to the measured value.
Factory setting: off (unlocked)
• DIP switch 2: damping on/off, factory setting: on (damping on)
8
Commissioning
8.1
Function check
The device is configured for the "Level" measuring mode as standard. The measuring range and
the unit in which the measured value is transmitted correspond to the data on the nameplate.
L
WARNING
The permitted process pressure is exceeded!
Risk of injury if parts burst! Warnings are displayed if the pressure is too high.
‣
If a pressure that is greater than the maximum permitted pressure is present at the device,
messages "E115 sensor overpressure" and "E727 sensor pressure error - overrange" are
output in succession. Only use the device within the sensor range limits!
NOTICE
The permitted process pressure is undershot!
Messages are displayed if the pressure is too low.
‣
If a pressure that is lower than the minimum permitted pressure is present at the device,
messages "E120 sensor low pressure" and "E727 sensor pressure error - overrange" are
output in succession. Only use the device within the sensor range limits!
8.2
Switching on the device
The device is switched on by connecting the supply voltage.
8.3
Device configuration
8.3.1
Level measuring mode
If no local display is connected, the following functions are possible via the three keys on the
electronic insert or externally on the device: