5 Commissioning
Hauser
26
5.1
Establishing communication via service interface
In order to establish communication with the Fieldgate via the service interface, a standard
9600 bit/s modem and a RTU (remote terminal unit) connection must be set up on your computer.
The following describes the procedure for Windows XP: for other Windows operating systems
consult your network administrator.
Once set up, the RTU connection can always be used for the service interface.
5.1.1
Connect the Fieldgate
Fieldgate is supplied with a PC service with a 9-pin sub-D female and 3-pin female connector. To
connect the Fieldgate to your computer:
1 Plug the 9-pin connector into the COM port (RS-232C) of your computer
2 Plug the 3-pin connector in the service port of the Fieldgate
–
This is located behind the front panel, see chap. 4.1.3
5.1.2
Set up a standard 9600 bps modem
Now set up a standard 9600 bps modem on your computer:
1 Select
Start > Settings > Control Panel> Telephone and Modem Options
:
2 If no modem has been set up on the computer the
Location Information
dialog appears:
–
Enter your location, city dialing code, carrier code (if required) and any number required to
dial out of your facility. Then check the appropriate dialing system.
–
Press
OK
to continue, the
Telephone and Modem Options
dialog appears.
–
If you are not sure of your data, check with your network administrator.