Modem Log
The modem log can be used to check the correct function of the Fieldgate with GSM modem. Up
to 25 lines are displayed. The log is deleted when the Fieldgate is switched off. Table 7-7 explains
the significance of the parameters.
Modem log message
Connection
Meaning
dial in (Server)
carrier lost (Server)
hangup requested by command (Server)
hangup (Server)
Modem/GSM
Diagnosis messages for dial-in with Fieldgate.
dial in disabled!
Modem/GSM
Fieldgate was called (with maximum number of
rings) but dial-in is not allowed.
assigned IP: <ip-addr>
carrier lost
hangup requested by command
hangup
connect failed
hangup requested by SMS transmission
hangup caused by PPP
Modem/GSM
Diagnosis messages for dial-in with ISP.
assigned IP: <ip-addr>
GPRS Network: <gprs network>
GPRS-QOS: <QOS> connect failed
GPRS hangup requested by ring or carrier loss
GPRS hangup requested by command
GPRS hangup requested by SMS transmission
GPRS hangup caused by PPP
GPRS hangup
GSM
Diagnosis messages for dial-in with GPRS.
initiating call back
Modem/GSM
Call-back to ISP started due to ringing.
No Signal!
GSM
The GSM module does not have any reception
signal.
Pin Ok
GSM
SIM Pin is OK.
User defined AT: <at-cmd>
Modem/GSM
User-defined AT commando output.
FAILED: timeout
Modem/GSM
Command at modem triggered a timeout.
FAILED: <modem-response>
Modem/GSM
Command at modem returned an unexpected
response.
OK: <modem-response>
Modem/GSM
Command at modem returned an expected
response.
GSM operator: <operator> signal = <signal
strength>
GSM
Output of current GSM operator and signal strength.
In order to ensure stable GSM operation the signal
strength should be > 15.
FAILED: no data call
GSM
Incoming call to Fieldgate without data connection
=> vocal call.
selected GSM operator denied, GSM Engine
switched to automatic mode
GSM
Manually set GSM Provider is not valid for the SIM
card in use.
cannot connect to selected GSM operator
connected to: <Provider>
or:
cannot connect to selected GSM operator, GSM
Engine switched to automatic mode
GSM
The GSM Modem cannot connect to the manually
entered provider. Possible reasons are a weak signal.
The Fieldgate has connected to an alternative
provider. In this case the GPRS connections are
suppressed..
Pin xxxx ist not correct-> ERROR
GSM
An attempt has been made to enter the PIN as xxxx,
which is presumably not the correct code.
Last retry to set a correct PIN
GSM
After the next incorrect attempt to enter the PIN,
the SIM card is locked .