5 Commissioning
Fieldgate FXA320
47
Hauser
5.5
Miscellaneous server settings
The
Network
menu contains two additional server setups that can be configured as required.
5.5.1
Time Server Setup
Fieldgate can automatically synchronise its time on every new start with the aid of a time server.
An Internet connection or a time server in the local network is required for this. Hauser
has its own time server, IP address= 62.154.220.81, which we recommend that you use. If you
have any questions, please contact your network administrator.
Procedure
1 If not already active, press
Switch to Administrator Mode => Settings
=> Network
– Scroll down to reveal the
Time Server Setup
page.
– Enter your settings and confirm with
Send
2 A manual time setting can be entered as follows:
– If Fieldgate is scanning, switch it off temporarily as described in Chapter 6.3.4
– Set
Protocol
to the option "manual"
– Enter the time stamp in the field provided, see also the table below
– Confirm the setting with
Send
Time server setup
Parameter
Description
Time Server
Enter the IP address of the time server here.
Protocol
Set the protocol used by the time server here:
– manual: Manual time setting.... timing is restarted with settings entered in "manual
Timestamp"
The time server operator can tell you the protocol the server uses.
Periodic Fetch
Enter the time interval after which the internal clock is to be resynchronised with the
time server
• Note: every synchronization causes a data transfer of several kBytes which is debited
from your SIM card or GPRS account.
Time Zone Setting ...
If appropriate, enter the time zone for which the http service is valid
– Enter the English name of the city the Windows Time Zone list nearest your location
– The list is opened by Settings => Control Panel => Time and Date => Time Zone
Time Offset
If appropriate, enter an offset from UTC time here
Date/Time format
Select the date and time format to be used in the Web pages from the drop-down menu
Manual Timestamp
If no time server is available in the LAN (Protocol = manual), set the time manually here.
– Format: dd.mm.yyyy hh:mi:ss
– If the Fieldgate is switched off, the manually set time is lost.
Содержание Fieldgate FXA320
Страница 6: ...Fieldgate FXA320 Endress Hauser 4 ...
Страница 104: ......
Страница 105: ......
Страница 106: ...Fieldgate FXA320 12 Appendix Endress Hauser 104 www endress com worldwide ...