4 Hardware Installation
Fieldgate FXA320
21
Hauser
4.2
Wiring
4.2.1
Terminals
Table 4-1 provides an overview of the Fieldgate terminals.
Table 4-1: Fieldgate terminals
4.2.2
Power supply and relay
Wire according to Fig. 4-5.
• Use a circuit breaker to isolate Fieldgate from line voltage when, e.g. wiring up.
• For switching capacity of NC relay see Table 4-1 above
• For mains supplied FXA320 Device, the user must install an external 1 A slow-blow fuse in the
power line. The fuse must be designed for min. 250 V and be approved for the application in
question.
• A total voltage of relay output and power supply lower than 300 V must be granted at
installation.
Fig. 4-5: Wiring up of power supply and relay
Location
No
Function
Remarks
1
1
Power L+/L1
Depending on device type, see nameplate on side:
• 20...60 VDC, 20...30 VAC
• 85...253 VAC, 50/60 Hz
• 10...30 VDC
2
Power L–/N
7
+
CH 1: Externally powered 4...20 mA device
8
–
9
+
CH 1: Loop-powered 4...20 mA device
10
–
11
+
CH 2: Externally powered 4...20 mA device
12
–
13
+
CH 2: Loop-powered 4...20 mA device
14
–
15
NC relay
• Max. 253 VAC, max. 2 A,
max. 500 VA at cos
ψ
=
0.7
• Max. 40 VDC, max. 2 A, max. 80 W
16
NC relay
22
BI1
Binary input 1
23
BI2
Binary input 2
24
GND
Ground, binary inputs 1 and 2
26
BI3
Binary input 3
27
BI4
Binary input 4
28
GND
Ground, binary inputs 3and 4
26
27
28
1
2
15
16
L
D
FXA320 ANALOG
22
23
24
7
8
9
10
11
12
13
14
L–
N
N
U~ 85…253 V
50/60 Hz
U– 20… 60 V
U~ 20… 30 V
50/60 Hz
(AC)
(DC)
(AC)
L+
L1
L1
...
15 16
N
1
L1
L+
L-
2
Power: check nameplate
...
U– 10… 30 V (DC)
solar power