9 Trouble-Shooting
Fieldgate FXA320
91
Hauser
9.2
Reset
The device is reset with button (7) and LED (2). If the button is pressed and held during when the
Fieldgate is started up, the following functions are available in the time frame when the button is
released:
Table 9-1: Fieldgate reset function
The red LED flashes at approx. 10 Hz during initialization once the button has been released or a
restart has taken place without pressing the button. This takes approx. 10 s. It takes approx. 30 s if
a firmware update was carried out.
Time frame
No.
Time frame Red LED
Function - release button
1
0 ... 5
Flashes at approx. 5 Hz
The data of the internal EEPROM is first checked, the configuration
data is copied from the internal EEPROM to the DAT module
2
5 ... 10
Off
No function when released
3
10 ... 15
Flashes at approx. 2.5 Hz
Configuration is reset to the factory settings
4
15 ... 20
Off
No function when released
5
20 ... 25
Flashes at approx. 1.25 Hz Firmware and configuration is reset to the factory settings
6
25 ... ...
Off
No function when released
7
8
1 2 3
4 5
CH 1
CH 2
6
9
0
5
10
15
20
25
t [s]
5
4
1
2
3
6