Deltabar FMD72
Commissioning
57
Prerequisite:
• The tank can be filled or emptied. The linearization characteristic must rise or fall continuously.
• The "Level" measuring mode has been selected.
• Level calibration is performed (see section from (
• For a description of the parameters mentioned, see "Description of device parameters" (
Description
1
Select the "Semiautom. entry" option via the "Lin.
mode (037)" parameter.
Menu path: Setup
®
Extended Setup
®
Linearization
®
Lin. Mode
3.5
0
0
3
V
[m3]
h
[m]
A0017669
2
Select using the "Unit after lin. (038)" parameter, e.g.
m
3
.
Menu path: Setup
®
Extended Setup
®
Linearization
®
Unit After Lin.
3
Fill the tank to the height of the 1st point.
4
Enter the number of the point in the table (e.g. 1)
using the "Line numb. (039)" parameter, .
Menu path: Setup
®
Extended Setup
®
Linearization
®
Line-numb
3.5
0
0
3.0
V
[m3]
h
[m]
20
4
I
[mA]
0
3.5
V
[m3]
A0017670
The level at the current time is displayed using the
"X-value (193)" parameter.
Menu path: Setup
®
Extended Setup
®
Linearization
®
X-value
Using the "Y-val. (041)" parameter, enter the
corresponding volume value, here 0 m3 for
example, and confirm the value.
Menu path: Setup
®
Extended Setup
®
Linearization
®
Y-val.
5
To enter another point in the table, continue filling
the tank and select the "Next point" option via the
"Edit Table (042)" parameter. Enter the next point
as explained in Step 4.
Menu path: Setup
®
Extended Setup
®
Linearization
®
Edit Table
6
Once all the points have been entered in the table,
select the "Activate table" option via the "Lin. mode
(037)" parameter.
Menu path: Setup
®
Extended Setup
®
Linearization
®
Lin. Mode
7
Result:
Result: The measured value after linearization is
displayed.
• Error message F510 "Linearization" and alarm current as long as the table is being entered
and until the table is activated.
• The lower range value (= 4mA) is defined by the smallest point in the table.
The upper range value (= 20mA) is defined by the greatest point in the table.
• Using the parameters "Set LRV" and "Set URV", you can change the allocation of the volume/
mass values to the current values.