Operation with an operating menu
Deltabar FMD72
34
9.6
Operation using Field Xpert SFX100
Compact, flexible and robust industry handheld terminal for remote configuration and for obtaining
measured values via the HART current output (4-20 mA).
For details, see Operating Instructions BA00060S/04/EN.
9.7
Direct access to parameters
The parameters can only be accessed directly via the "Expert" user role.
Direct access (119)
Navigation
Expert
®
Direct Access
Read permission
Operators/Service engineers/Expert
Write permission
Operators/Service engineers/Expert
Description
Enter the direct access code to go directly to a parameter.
Options
Enter the desired parameter code.
Factory setting
0
Note
For direct access, it is not necessary to enter leading zeros.
9.8
Locking/unlocking operation
Once you have entered all the parameters, you can lock your entries against unauthorized and
undesired access.
You have the following options for locking/unlocking operation:
• Via the DIP switch on the electronic insert, local at the device.
• Via the local display (optional)
• Via communication e.g. FieldCare and HART handheld terminal.
The
-symbol on the onsite display indicates that operation is locked. Parameters which refer to
how the display appears, e.g. "Language" and "Display contrast", can still be altered.
If operation is locked by means of the DIP switch, you can only unlock operation again by
means of the DIP switch. If operation is locked by means of local display or remote operation
e.g. FieldCare, you can unlock operation either using the local display or remote operation.
The "Operator Code" parameter is used to lock and unlock the device.
The parameters can only be accessed directly via the "Expert" user role.
Operator Code (021)
Navigation
Setup
®
Advanced Setup
®
Operator Code
Read permission
Operators/Service engineers/Expert