Deltabar FMD72
Operation with an operating menu
33
Pos. Zero Adjust
007
Operation
4
Â
Cancel
Exit edit mode for the parameter with
F
.
Confirm
User-definable parameters
Example: setting parameter "Set URV (014)" from 100 mbar (1.5 psi) to 50 mbar (0.75 psi).
Menu path: Setup
È
Advanced. Setup
È
Current output
È
Set URV
Set URV
014
Operation
The onsite display shows the parameter to be changed. The "mbar" unit
is defined in another parameter and cannot be changed here.
1
1 0 0 . 0 0 0
mbar
Press
O
or
S
to get to edit mode. The first digit is highlighted in black.
2
1
0 0 . 0 0 0
mbar
Use the
O
key to change "1" to "5". Press the
F
key to confirm "5".
Cursor jumps to the next position. Use the
F
key to confirm (second
position).
3
5
0 0 . 0 0 0
mbar
The third digit is highlighted in black and can now be edited.
4
5 0
0
. 0 0 0
mbar
Use the
S
key to change to the "
¿
" symbol. Use
F
to save the new value
and exit edit mode. See next graphic.
5
5 0
¿
. 0 0 0
mbar
The new value for the full scale value is 50.0 mbar (0.75 psi). Exit edit
mode for the parameter with
F
. You can get back to edit mode with
O
or
S
.
6
5 0 . 0 0 0
mbar
9.5
Operation using Hauser operating program
The FieldCare operating program is an Hauser plant asset management tool based on FDT
technology. With FieldCare, you can configure all Hauser devices as well as devices from
other manufacturers that support the FDT standard.
Hardware and software requirements can be found on the Internet:
www.de.endress.com
È
Search: FieldCare
È
FieldCare
È
Technical data.
FieldCare supports the following functions:
• Configuration of transmitters in online/offline mode
• Loading and saving device data (upload/download)
• Documentation of the measuring point
Connection options:
• HART via Commubox FXA195 and the USB port on a computer
• HART via FXA520 Fieldgate
• "Connecting the Commubox FXA195" (
• Additional information about FieldCare can be found on the Internet:
http://www.de.endress.com
È
Download
È
Search: FieldCare
• As not all internal device dependencies can be mapped in offline operation, the consistency
of the parameters must be checked before the parameters are transmitted to the device.
Содержание Deltabar FMD72
Страница 2: ......
Страница 107: ......
Страница 108: ...www endress com worldwide 71191239 71191239 BA01044P 00 EN 02 12 71191239 CCS COSIMA...