Commissioning
Deltabar FMD72
48
• The values entered for "Empty Calib./Full Calib.", "Empty Pressure/Empty Pressure" and
"Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a warning
message displayed, if the values are too close together. Further limit values are not checked,
i.e. the values entered must be appropriate for the sensor module and the measuring task for
the device to be able to measure correctly.
• Due to the orientation of the device, there may be pressure shifts in the measured value, i.e.
when the container is empty or partly filled, the measured value is not zero. For information
on how to perform position adjustment, see (
Description
1
Select the "Level" measuring mode via the
"Measuring mode (005)" parameter.
Menu path: Setup
®
Measuring Mode
0 L
1000 L
450 mbar
50 mbar
1
2
3
r
= 1
g
cm
A0017661
1
See table, steps 6 and 7.
2
See table, steps 8 and 9.
2
Select a pressure engineering unit via the "Press Eng.
Unit (125)" parameter, here "mbar" for example.
Menu path: Setup
®
Press Eng. Unit
3
Select the "In pressure" level mode via the "Level
Selection (024)" parameter.
Menu path: Setup
®
Extended Setup
®
Level
®
Level Selection.
4
Select a volume unit via the "Unit before lin. (025)"
parameter, here "l" (liters) for example.
Menu path: Setup
®
Extended Setup
®
Level
®
Unit before lin.
5
Select the "Dry" option via the "Calibration mode
(027)" parameter.
Menu path: Setup
®
Extended Setup
®
Level
®
Calibration Mode
1000
0
V
[l]
50
450
p
[mbar]
20
4
I
[mA]
0
1000
V
[l]
A0017662
1
See table, step 6.
2
See table, step 7.
3
See table, step 8.
6
Enter the volume value for the lower calibration
point via the "Empty Calib. (028)" parameter, here
0 liters for example.
Menu path: Setup
®
Extended Setup
®
Level
®
Empty Calibration
7
Enter the pressure value for the lower calibration
point via the "Empty Pressure (029)" parameter,
here 50 mbar (0.75 psi), for example.
Menu path: Setup
®
Extended Setup
®
Level
®
Empty Pressure
8
Enter the volume value for the upper calibration
point via the "Full Calib. (031)" parameter, here
1000 liters (264 gal) for example.
Menu path: Setup
®
Extended Setup
®
Level
®
Full Calibration
9
Enter the pressure value for the upper calibration
point via the "Full Pressure (032)" parameter, here
450 mbar (6.75 psi), for example.
Menu path: Setup
®
Extended Setup
®
Level
®
Full Pressure
10
"Adjust density (034)" contains the factory setting
1.0, but this value can be changed if required.
Menu path: Setup
®
Extended Setup
®
Level
®
Adjust Density