41521-2-0520
Page 18
INSTALLATION (CONT’D)
ON TOP AND SIDES AND
BETWEEN 1/2” TO 3/4” AT BOTTOM
Figure 21
Horizontal Vent Clearance
For horizontal vent, maintain 1 inch of clearance to the bottom
and sides of vent, and 6 inches of clearance to combustibles
above the vent pipe.
See Figure 223.
Vertical Vent Clearance
For vertical vent, maintain a minimum 1 of inch clearance to
combustibles.
NOTICE:
Maintain 1 of inch of clearance to combustibles around
vertical vent pipe.
See Figure 22.
For horizontal vent systems,
maintain a minimum 1 inch of clearance from the bottom and sides
of the vent to combustibles and a 3 inches of
clearance above the
vent pipe
to combustibles.
See Figures 22 and 23.
VENT PIPE
1” MINIMUM CLEARANCE
AROUND VENT PIPE
Figure 22
TOP OF VENT
COMBUSTIBLES NOT
ALLOWED IN SHADED
AREA
6” (152 mm)
8” DIAMETER
INTAKE VENT
1” (25 mm)
5” DIAMETER FLUE
1” (25 mm)
Horizontal Vent Clearances - Figure 23
NOTE:
Top clearance through outside wall is 3 inches.
ATTENTION:
Cold climate installation recommendation: When
installing this unit against an exterior wall, the exterior wall must
be insulated to conform to applicable insulation codes. The
fireplace outer wrapper is not considered a thermal barrier and
can allow air infiltration. Care should be taken to properly seal
the chase area so air infiltration is kept to a minimum and drafts
do not occur through the fireplace.
Vent Runs
In planning the installation, you must install certain components
before the fireplace is secured in position. These include the
direct-vent system, gas piping, and the electrical wiring.
The appliance can be mounted on any of the following surfaces:
1. A flat, hard combustible or non-combustible surface.
2. A raised wooden platform.
3. Four corner supports(such as masonry blocks). These supports
must be positioned so they contact all four perimeter edges on
the bottom of the unit.
OVERLAP TOP EDGE OF
NON-COMBUSTIBLE
BOARD WITH EXTERIOR
WEATHER BARRIER
SEAL THE PERIMETER OF
THE OUTDOOR KIT WITH
(300°F (149°C) SEALANT
FACING MATERIAL MUST
OVERLAP THE OUTDOOR
KIT PERIMETER BY AT
LEAST 1" ON TOP AND
SIDES AND BETWEEN 1/2"
TO 3/4" AT BOTTOM
FACING MATERIAL MAY
OVERLAP THE OUTDOOR
KIT UP TO 1/2" AWAY FROM
THE KIT OPENING
SEAL THE INTERFACE
BETWEEN THE OUTDOOR
KIT AND THE FACING
MATERIAL WITH AN
EXTERIOR CAULK