41521-2-0520
Page 13
GAS SUPPLY
The gas pipeline can be brought in through the right side of the
fireplace. The fireplace has a Flexline with shut-off valve located
on the right side when facing the fireplace.
See Figures 7.
Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/
CGA-B149 (.1 or .2) installation code.
CAUTION
Never use plastic pipe. Check to confirm whether your local
codes allow copper or galvanized tubing.
NOTICE:
Some municipalities have additional local codes.
Consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANSI Z21.24 Fireplace Connectors of Corrugated Metal
Tubing and Fittings.
— ANSI Z21.45 Assembled Flexible Fireplace Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The Commonwealth of Massachusetts requires
that a flexible fireplace connector cannot exceed three feet in length.
Figure 7
Installing the Main Gas Shut-Off
Each fireplace should have its own manual gas shut-off.
A manual main gas shut-off should be located in the vicinity of the
fireplace and can be easily accessed. Where none exists, or where
its size or location is not adequate, contact your local authorized
installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. Testing for leaks on all exposed
connections should be done with leak test solution or a soap
solution. After testing is complete, all solution should be cleaned off.
On unexposed connections, a pressure test should be made.
WARNING
Never use an exposed flame to check for leaks. Fireplace
must be disconnected from piping at inlet of control valve and
pipe capped or plugged for pressure test. Never pressure test
with fireplace connected; control valve will sustain damage.
NOTICE:
The gas controls are equipped with a captured screw-
type pressure test point. It is not necessary to provide a 1/8-inch
test point up stream of the control.
When using copper or flex connector use only approved fittings.
The fireplace and its individual shut-off valve must be
disconnected from supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig
(3.5kPa).
The fireplace must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test pressures
equal to or less than 1/2 psig (3.5kPa).
WARNING
If one of the procedures results in pressures in excess of
1/2 psig (14 inches w.c.) (3.5 kPa) on the fireplace gas valve,
it will result in a hazardous condition.
LEFT SIDE OF FIREPLACE
FRONT
OF FIREPLACE
GAS FLEX
LINE WITH
SHUT-OFF VALVE
(PROVIDED)
11 3/4”
19 3/8”
Figure 8
A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. The National
Fuel Gas Code requires that a drip leg be installed near the gas
inlet.
See Figure 9.
This should consist of a vertical length of
pipe tee connected into the gas line that is capped on the bottom
in which condensation and foreign particles may collect.
GAS SUPPLY PLUMBING
MANUAL
SHUT-OFF VALVE
GAS SUPPLY
INLET
DRIP LEG
3” MINIMUM
TO CONTROL
VALVE
Figure 9
6 13/16"
20"