4
Maintenance and troubleshooting
This chapter deals with preventative maintenance, describes possible faults in detector
operation, and indicates corrective measures.
Ignoring these instructions may cause problems with the detector and may invalidate the
warranty. Whenever a unit requires service, please contact Emerson or its authorized
distributer for assistance.
4.1
Maintenance
This section describes the basic maintenance steps you should take to keep the detector in
good working condition.
4.1.1
General maintenance procedures
Only suitably qualified personnel who are familiar with local codes and practices should
perform maintenance. Maintenance requires ordinary tools.
Cleaning
Keep the detector as clean as possible. Clean the viewing window and the reflector of the
flame detector periodically.
The frequency of cleaning operations depends upon the local environmental conditions
and specific applications. The fire detection system designer will give his or her
recommendations.
To clean the detector viewing window and reflector:
Procedure
1. Disconnect power to the detector before proceeding with any maintenance,
including window/lens cleaning.
2. Use water and detergent and then rinse the viewing window with clean water.
3. Where dust, dirt, or moisture accumulates on the window, first clean only with a
soft optical cloth and detergent and then rinse with clean water.
4.1.2
Periodic maintenance procedures
In addition to preventive cleaning and maintenance, functionally test the detector every
six months or as dictated by local codes and regulations. Also perform these tests if the
detector has been opened for any reason.
Power-up procedure
Perform the power-up procedure every time power is restored to the system.
Follow the instructions described in
Reference Manual
Maintenance and troubleshooting
00809-0100-4976
June 2021
Rosemount 975HR
47
Legacy
Содержание Rosemount 975HR
Страница 28: ...Introduction Reference Manual June 2021 00809 0100 4976 28 Emerson com Rosemount L e g a c y ...
Страница 42: ...Installing the detector Reference Manual June 2021 00809 0100 4976 42 Emerson com Rosemount L e g a c y ...
Страница 66: ...RS 485 communication network Reference Manual June 2021 00809 0100 4976 66 Emerson com Rosemount L e g a c y ...
Страница 78: ...SIL 2 features Reference Manual June 2021 00809 0100 4976 78 Emerson com Rosemount L e g a c y ...