3. Wait 20 seconds before repeating the test.
4. Verify that the optical window is clean.
D.1.4
Range
Table D-1: Sensitivity Ranges
Sensitivity
Detection range (ft. / m)
Standard test range (ft. / m)
1 (low)
50 / 15
6.6 / 2
2
100 / 30
19.6 / 6
3
150 / 45
29.5 / 9
4 (high)
200 / 60
39.3 / 12
1. The minimum distance from the detector is 20 in. (50 cm).
2. At extreme temperatures, there is a 15 percent maximum reduction in the range.
NOTICE
Keep the flame simulator in a safe place when not in use.
D.1.5
Charge the battery
The flame simulator uses lithium ion batteries as a rechargeable power source. When the
batteries are fully charged, the simulator operates for at least 1,000 times without having
to be recharged. The simulator will not operate when the voltage from the batteries is
lower than the required operational level.