Sensors
•
Window cleanliness
The detector can be set to perform the built-in test in the following modes:
•
Automatically and manually
•
Manually only
NOTICE
In a manual built-in test, the outputs may also be tested; apply control system
inhibit
if
this could initiate other systems.
How the built-in test operates
•
The detector's status remains unchanged if the result of a built-in test is the same as
the current status (Normal or BIT Fault).
•
The detector's status is changed (from Normal to BIT Fault or vice versa) if the built-in
test differs from the current status.
NOTICE
In BIT Fault status, the detector can continue to detect a fire.
Automatic built-in test
The detector automatically performs a built-in test every fifteen minutes. A successful
built-in test sequence does not activate any indicator.
All outputs of built-in test results function as described in
the built-in test is automatically executed every one minute.
This continues until a successful built-in test occurs, when the detector resumes normal
operation.
Table 1-9: Results of a Successful Built-in Test
Output
Result
Fault relay
•
Output configurations 1A, 2A, and 1R:
remain CLOSED
•
Output configurations 3A and 2R: remain
OPEN
0-20 mA output
Output configurations 1A, 2A, and 3A: Normal
(4 mA)
Power LED
Green, flashing, 1 Hz on (Normal)
Introduction
Reference Manual
June 2021
00809-0100-4976
26
Emerson.com/Rosemount
Legacy
Содержание Rosemount 975HR
Страница 28: ...Introduction Reference Manual June 2021 00809 0100 4976 28 Emerson com Rosemount L e g a c y ...
Страница 42: ...Installing the detector Reference Manual June 2021 00809 0100 4976 42 Emerson com Rosemount L e g a c y ...
Страница 66: ...RS 485 communication network Reference Manual June 2021 00809 0100 4976 66 Emerson com Rosemount L e g a c y ...
Страница 78: ...SIL 2 features Reference Manual June 2021 00809 0100 4976 78 Emerson com Rosemount L e g a c y ...