Installing the detector
This chapter provides basic guidelines for installing the detector. It does not attempt to
cover all of the standard practices and codes of installation. Rather, it emphasizes specific
points of consideration and provides some general rules for qualified personnel. Wherever
applicable, special safety precautions are stressed.
2.1
General guidelines
To ensure optimal performance and an efficient installation, consider the following
guidelines:
•
Sensitivity: To determine the level of sensitivity, consider the following:
—
Size of fire at the required distance to be detected
—
Type of flammable materials
•
Wiring:
—
The wire gauge must be designed according to the distance from the detector to
the controller and the number of detectors on the same power line. See
.
—
To fully comply with EMC directive and protect against interference caused by RFI
and EMI, the cable to the detector must be shielded, and the detector must be
grounded. Ground the shield at the detector end.
•
Spacing and location: The number of detectors and their locations in the protected
area are determined by:
—
Size of the protected area
—
Sensitivity of the detectors
—
Obstructed lines of sight
—
Cone of view of the detectors
•
Environment:
—
Dust, snow, or rain can reduce the detector's sensitivity and require more
maintenance activities.
—
The presence of high intensity flickering IR sources may affect sensitivity.
•
Aiming the detector:
—
Aim the detector toward the center of the detection zone and make sure the view
of the protected area is completely unobstructed.
—
Whenever possible, tilt the detector face down at a 45-degree angle to maximize
coverage and prevent accumulation of dust and dirt.
—
Take into account all conceivable considerations regarding detection location
before starting an installation.
Installations must comply with National Fire Protection Agency (NFPA) 72E or any other
local and international regulations and standards, as applicable to flame detectors and
installation of Ex approved products.
Reference Manual
Installing the detector
00809-0100-4976
June 2021
Rosemount 975HR
29
Legacy
Содержание Rosemount 975HR
Страница 28: ...Introduction Reference Manual June 2021 00809 0100 4976 28 Emerson com Rosemount L e g a c y ...
Страница 42: ...Installing the detector Reference Manual June 2021 00809 0100 4976 42 Emerson com Rosemount L e g a c y ...
Страница 66: ...RS 485 communication network Reference Manual June 2021 00809 0100 4976 66 Emerson com Rosemount L e g a c y ...
Страница 78: ...SIL 2 features Reference Manual June 2021 00809 0100 4976 78 Emerson com Rosemount L e g a c y ...