Temperature: 2 (185 °F [85 °C])
•
Approvals: A1 (ATEX and IECEx flameproof)
NOTICE
Check your specific part numbers against the information in
.
1.3
Features and benefits
The flame detector has the following features and benefits.
•
Detects hydrocarbons and hydrogen flames.
•
Detection range: Up to 215 ft. (65 m) for a 1 ft.
2
(0.1 m
2
) n-heptane fire.
•
Ultra high immunity to false alarms. See
.
•
Advanced digital processing of the dynamic characteristics of fire: flickering, threshold,
correlation, and ratio.
•
Multi infrared channels: between two and five microns.
•
Field programmable sensitivity: four ranges to avoid zone crossover.
•
Built-in-test (BIT): manual and automatic (see
).
•
Heated window: prevents effects of icing, snow, and condensation.
•
Electrical interface:
—
Dry contact relays
—
Communication network RS-485
—
0-20 mA output
•
HART
®
protocol: communication protocol (see
•
Exde: integral junction box for easy wiring.
•
SIL-2: TÜV approved.
•
Hazardous area certification: ATEX, IECEx, FM, and CSA.
•
Functionality approval:
—
EN54-10 approved by VdS
—
FM approved per FM3260
•
Accessories are approved as part of ATEX and IECEx approval.
1.4
Principles of operation
1.4.1
Fire detection principle
Emerson designed this flame detector to detect hydrocarbon flames that produce CO
2
in
their combusion process and non-hydrocarbon flames that produce mainly water vapor
Reference Manual
Introduction
00809-0100-4976
June 2021
Rosemount 975HR
11
Legacy
Содержание Rosemount 975HR
Страница 28: ...Introduction Reference Manual June 2021 00809 0100 4976 28 Emerson com Rosemount L e g a c y ...
Страница 42: ...Installing the detector Reference Manual June 2021 00809 0100 4976 42 Emerson com Rosemount L e g a c y ...
Страница 66: ...RS 485 communication network Reference Manual June 2021 00809 0100 4976 66 Emerson com Rosemount L e g a c y ...
Страница 78: ...SIL 2 features Reference Manual June 2021 00809 0100 4976 78 Emerson com Rosemount L e g a c y ...