Operating temperature: +167 °F (+75 °C)
•
Storage temperature: +185 °F (+85 °C)
Low temperature
•
Designed to meet DNVGL-CG-0339, class D
•
Operating temperature: -57 °F (-50 °C)
•
Storage temperature: -65 °F (-55 °C)
Humidity
The Rosemount 975 detector conforms to DNVGL-CG-0339, class B.
Enclosure
The Rosemount 975 detector conforms to DNVGL-CG-0339, class C.
Water and dust
•
IP66 per EN60529
•
IP68 per EN60529
•
Dust: Completely protected against dust.
•
Liquids: Protected against immersion between 6 in. (15 cm) and
3 ft. (1 m) in depth. Protected against water jets from all
directions.
Vibration
The Rosemount 975 detector conforms to DNVGL-CG-0339, class B.
Table A-5: Electromagnetic Compatibility
This product is in conformance with EMC per EN50270.
Level per
Radiated immunity
EN61000-4-3
Conducted immunity
EN61000-4-6
Electrostatic discharge (ESD)
EN61000-4-2
Magnetic field
EN61000-4-8
Burst
EN61000-4-4
Surge
EN61000-4-5
Radiated emission
EN550022
Conducted emission
EN550022
CAUTION
To fully comply with EMC directive 2014/30/EU and protect against interference caused by
radio frequency interference and electromagnetic interference, shield the cable to the
detector and ground the detector. Ground the shield at the detector end.
Reference Manual
Specifications and reference data
00809-0100-4976
June 2021
Rosemount 975HR
55
Legacy
Содержание Rosemount 975HR
Страница 28: ...Introduction Reference Manual June 2021 00809 0100 4976 28 Emerson com Rosemount L e g a c y ...
Страница 42: ...Installing the detector Reference Manual June 2021 00809 0100 4976 42 Emerson com Rosemount L e g a c y ...
Страница 66: ...RS 485 communication network Reference Manual June 2021 00809 0100 4976 66 Emerson com Rosemount L e g a c y ...
Страница 78: ...SIL 2 features Reference Manual June 2021 00809 0100 4976 78 Emerson com Rosemount L e g a c y ...