FloBoss 407 Instruction Manual
A-4
Rev 5/00
A.5 TROUBLESHOOTING AND REPAIR
The lightning protection modules function by shunting the high voltage transients through gas discharge
tubes to the ground lead. In the event of an I/O signal failure, verify the signal is not interrupted by the
LPM. Proceed to the troubleshooting and repair procedures for I/O in previous sections of this manual.
Before removing an LPM, make sure all devices and processes remain in a safe state. Remove the
LPM and disconnect the field wiring. Remove any range resistors from the LPM. With a digital
multimeter, verify continuity through each connector socket to the corresponding field wiring terminal.
If there is no continuity, replace the LPM.
With a digital multimeter, check each of the input terminals for continuity to the ground lead. If the test
shows continuity to the ground lead, replace the LPM.
A.6 SPECIFICATIONS
The following specifications are for the LPM.
Specifications
ELECTRICAL
Series Resistance:
10 ohms from
input to output, each terminal.
DC Clamping Voltage:
72 to 108
volts.
100 V/ms Impulse Clamping
Voltage:
500 volts maximum.
Clamping Release Voltage:
52
volts minimum.
10 KV/microsecond Impulse
Clamping Voltage:
900 volts
maximum.
Surge Life:
Module can withstand
300 surges of 10 to 1000 micro-
seconds duration at 500 amps
minimum.
Insulation Resistance:
10,000
megohm minimum.
Capacitance:
1.0 picofarad
maximum
@
1 MHz, each terminal.
CASE
SURGE
WITHSTAND
ENVIRONMENTAL
WEIGHT
APPROVALS
Material:
ABS polycarbonate
thermoplastic.
Dimensions:
0.65 in. H by 0.84
in. W by 1.58 in. D (17 mm by 21
mm by 40 mm).
Length of Ground Wire:
48
inches (1.2 m) nominal.
Meets surge requirements
CCITT K17-K20.
Operating Temperature:
-40 to
75 °C (-40 to 167 °F).
Storage Temperature:
-60 to
100 °C (-76 to 212 °F).
Operating Humidity:
To 95%
relative, non-condensing.
1.2 ounces (34 grams).
Approved by CSA for hazardous
locations Class I, Division 2,
Groups A, B, C, and D.
Содержание Fisher FLOBOSS 407
Страница 6: ...FloBoss 407 Instruction Manual vi Rev 5 00 This page is intentionally left blank ...
Страница 22: ...FloBoss 407 Instruction Manual 1 16 Rev 5 00 This page intentionally left blank ...
Страница 134: ...FloBoss 407 Instruction Manual 4 24 Rev 5 00 This page is intentionally left blank ...
Страница 160: ...FloBoss 407 Instruction Manual B 4 Rev 5 00 DOC0326A Figure B 4 Pipe Mounting of FloBoss 407 with Integral MVS ...
Страница 184: ...FloBoss 407 Instruction Manual C 8 Rev 5 00 This page is intentionally left blank ...
Страница 190: ...FloBoss 407 Instruction Manual G 6 Rev 5 00 This page is intentionally left blank ...
Страница 199: ...FloBoss 407 Instruction Manual Rev 5 00 I 9 This page intentionally left blank ...