FloBoss 407 Instruction Manual
Rev 5/00
3-23
3.4.14 Low-Level Pulse Input Module
A schematic representation of the field wiring connections to the input circuit of the Low-Level Pulse
Input module is shown in Figure 3-20. The field wiring connections are made through a separate
terminal block that plugs in next to the module allowing replacement of the module without
disconnecting field wiring.
NOTE
The Low-Level Pulse Input
module is designed to operate only with pulse-
generating devices having their own power source. The module does not work with
non-powered devices.
The low-level pulse input module operates when a field device provides a pulsed voltage between
30 millivolts and 3 volts peak-to-peak across terminals B and C of the module. The pulsed voltage is
counted and accumulated by the module, which provides the accumulated count to the ROC/FloBoss
electronics on request.
SELF-POWERED
PULSE DEVICE
+
–
+
C
B
–
A
N/C
200K
200K
DOC0150A
PI LL
Figure 3-20. Low-Level Pulse Input Module Field Wiring Schematic
Содержание Fisher FLOBOSS 407
Страница 6: ...FloBoss 407 Instruction Manual vi Rev 5 00 This page is intentionally left blank ...
Страница 22: ...FloBoss 407 Instruction Manual 1 16 Rev 5 00 This page intentionally left blank ...
Страница 134: ...FloBoss 407 Instruction Manual 4 24 Rev 5 00 This page is intentionally left blank ...
Страница 160: ...FloBoss 407 Instruction Manual B 4 Rev 5 00 DOC0326A Figure B 4 Pipe Mounting of FloBoss 407 with Integral MVS ...
Страница 184: ...FloBoss 407 Instruction Manual C 8 Rev 5 00 This page is intentionally left blank ...
Страница 190: ...FloBoss 407 Instruction Manual G 6 Rev 5 00 This page is intentionally left blank ...
Страница 199: ...FloBoss 407 Instruction Manual Rev 5 00 I 9 This page intentionally left blank ...