FloBoss 407 Instruction Manual
2-16
Rev 5/00
+
-
1 LIMIT
-
+
+T
+
-
ROC-POWERED
CURRENT LOOP
DEVICE
V
s
= 11 TO 30 VDC
+T = 24 VDC
+SIGNAL = 4 TO 20 mA
250 OHM
AI
V
s
DOC0098A
Modified
Figure 2-5. Current Signal on Built-in Analog Input
1 LIMIT
+
-
EXTERNAL/
SELF-POWERED
DEVICE
V
s
= 11 TO 30 VDC
+T = 24 VDC
+SIGNAL = 1 TO 5 VDC
AI
+T
+
-
V
s
DOC0098A
Modified
+
-
Figure 2-6. Voltage Signal on Built-in Analog Input
2.4.4 Built-in Pulse Inpu t Wiring
Equipment Required:
Flat-blade (1/8-inch width) screwdriver
Changing the P4 jumper to the “PI” position allows the built-in AI/PI input channel to be used as either
an isolated or a sourced pulse input. This pulse input signal is optically isolated from the FloBoss 407
circuit board. The pulse input can operate at up to 10 kHz, with a maximum 50% duty cycle.
The AI/PI channel has three field terminals. Terminal “+T” is a positive source voltage, 24
volts or a level that follows the voltage of the FloBoss 407 input power. Terminal “+” is the positive
signal input; terminal “-” is the negative signal input. Be sure to remove the supplied 250-ohm resistor
from the terminal block when using the AI/PI channel as a pulse input.
To use the channel as an isolated input shown in Figure 2-7, connect the “+” and “-” field wires to
terminals “+” and “-” on the FloBoss 407 Pulse Input channel. When the field device sends a voltage
through terminal “+” on activation, the PI indicator LED on the termination board lights to show an
active circuit and the signal triggers the optical circuitry to signal the FloBoss 407.
Содержание Fisher FLOBOSS 407
Страница 6: ...FloBoss 407 Instruction Manual vi Rev 5 00 This page is intentionally left blank ...
Страница 22: ...FloBoss 407 Instruction Manual 1 16 Rev 5 00 This page intentionally left blank ...
Страница 134: ...FloBoss 407 Instruction Manual 4 24 Rev 5 00 This page is intentionally left blank ...
Страница 160: ...FloBoss 407 Instruction Manual B 4 Rev 5 00 DOC0326A Figure B 4 Pipe Mounting of FloBoss 407 with Integral MVS ...
Страница 184: ...FloBoss 407 Instruction Manual C 8 Rev 5 00 This page is intentionally left blank ...
Страница 190: ...FloBoss 407 Instruction Manual G 6 Rev 5 00 This page is intentionally left blank ...
Страница 199: ...FloBoss 407 Instruction Manual Rev 5 00 I 9 This page intentionally left blank ...