FloBoss 407 Instruction Manual
2-20
Rev 5/00
PULSE INPUT INDICATOR
DOC0207A-mod
STATUS INDICATOR
POWER INDICATOR
LV START SWITCH
Figure 2-10. FloBoss 407 Indicator Locations
Table 2-3. Indicator Functions
INDICATOR
STATUS
DESCRIPTION
STATUS
ON
Successful startup and the processor is running.
STATUS
BLINKING
Processor is not running and is attempting to restart.
Can result from bad clock battery (see Section 2.5.7).
STATUS
OFF
No input power, circuit protection devices
overloaded, insufficient voltage available to power up
(see Section 2.5.3), or input power polarity reversed.
POWER
ON
Power is connected. Must be minimum of 12.5 volts,
unless LV START switch is used (see Figure 2-10
and Section 2.5.3).
POWER
OFF
Power not applied.
PI IND
ON
Input active.
PI IND
OFF
Input not active.