ISEL Function Block
November 2010
141
Table 4-40. Input Selector Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial
Value
Range
Block
Mode
RO /
RW
Index
Number
Disable Analog Input 8
DISABLE_8
32
ALL
Value
BAD
NC
constant
Data Type: DS-66
Enable/Disable for Input_8, If parameter is TRUE
then input is disabled. If parameter status is BAD it is
not evaluated.
Status
0=Use
1=Disable
0
Number used to average
AVG_USE
33
1 to 8
0
Data Type: Unsigned8
Number used to average the output. The number of
min and max dropped is the number of inputs minus
AVG_USE.
Alarm Summary
ALARM_SUM
34
Data Type: DS-74
Current alert status, unacknowledged states,
unreported states, and disabled states of the alarms
associated with the function block.
CURRENT
34.1
RO
NA
1: Hi Hi
2: Hi
3: Lo Lo
4: Lo
UNACKNOWLEDGED
34.2
RO
NA
UNREPORTED
34.3
RO
NA
DISABLED
34.4
RW
ALL
Acknowledge Option
ACK_OPTION
35
ALL
1: Hi Hi
2: Hi
3: Lo Lo
4: Lo
0
Data Type: Bit String
Selection of whether alarms associated with the block
will be automatically acknowledged.
0=Disable
1=Enable
Alarm Hysteresis
ALARM_HYS
36
ALL
0 to 50%
0.50%
Data Type: Float
Hysteresis on alarms
High High Priority
HI_HI_PRI
37
ALL
0 TO 15
0
Data Type: Unsigned8
Priority of the alarm
High High Limit
HI_HI_LIM
38
ALL
0
Data Type: Float
Value of analog input which will generate an alarm
High Priority
HI_PRI
39
ALL
0 TO 15
0
Data Type: Unsigned8
Priority of the alarm
High Limit
HI_LIM
40
ALL
0
Data Type: Float
Value of analog input which will generate an alarm
Low Priority
LO_PRI
41
ALL
0 TO 15
0
Data Type: Unsigned8
Priority of the alarm
Low Limit
LO_LIM
42
ALL
0
Data Type: Float
Value of analog input which will generate an alarm
Low Low Priority
LO_LO_PRI
43
ALL
0 TO 15
0
Data Type: Unsigned8
Priority of the alarm
Low Low Limit
LO_LO_LIM
44
ALL
0
Data Type: Float
Value of analog input which will generate an alarm
High High Alarm
HI_HI_ALM
45
Data Type: DS-71
The high high alarm data, which includes a value of
the alarm, a timestamp of occurrence, and the state
of the alarm.
UNACKNOWLEDGED
45.1
RW
N/A
0=Undefined
1=Acknowledged
2=
Unacknowledged
0
ALARM_STATE
45.2
RO
N/A
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported
0
TIME_STAMP
45.3
RO
N/A
0
SUBCODE
45.4
RO
N/A
0
VALUE
45.5
RO
N/A
0
−
Continued
−
4
Содержание FIELDVUE DVC6200f
Страница 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Страница 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Страница 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Страница 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Страница 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Страница 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Страница 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Страница 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Страница 251: ...Principle of Operation November 2010 239 A A Appendix A Principle of Operation Digital Valve Controller Operation 240 A ...
Страница 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Страница 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Страница 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Страница 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Страница 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Страница 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...
Страница 325: ...This page intentionally left blank ...