Installation
November 2010
19
Wiring and Electrical Connections
Fieldbus Connections
The digital valve controller is normally powered over
the bus from a fieldbus power supply. Refer to the site
planning guide for proper wire types, termination,
length, etc. for a fieldbus loop.
Note
As shipped from the factory, the
DVC6200f digital valve controller will
not move the valve when power is
applied to the instrument. To avoid the
valve going to an unknown position
when power is applied, the unit is
shipped from the factory with the
transducer block mode Out of Service.
See the Basic Setup section for
information on setup and calibration
and placing the instrument in service.
WARNING
To avoid personal injury resulting
from electrical shock, do not exceed
the maximum input voltage specified
in table 1-1 of this quick start guide,
or on the product nameplate. If the
input voltage specified differs, do not
exceed the lowest specified maximum
input voltage.
Personal injury or property damage
caused by fire or explosion may occur
if this connection is attempted in a
potentially explosive atmosphere or in
an area that has been classified as
hazardous. Confirm that area
classification and atmosphere
conditions permit the safe removal of
the terminal box cover before
proceeding.
GE41456_A
SAFETY
GROUND
LOOP
LOOP
TALK
TALK
EARTH
GROUND
Figure 2-8. Loop Connections Terminal Box
WARNING
Select wiring and/or cable glands that
are rated for the environment of use
(such as hazardous area, ingress
protection and temperature). Failure
to use properly rated wiring and/or
cable glands can result in personal
injury or property damage from fire or
explosion.
Wiring connections must be in
accordance with local, regional, and
national codes for any given
hazardous area approval. Failure to
follow the local, regional, and national
codes could result in personal injury
or property damage from fire or
explosion
Making Fieldbus Connections with
Twisted Shielded Pair
Refer to figure 8-2 for identification of parts.
Wire the digital valve controller as follows, refer to
figure 2-8:
1. Remove the wiring terminal box cap.
2. Bring the field wiring into the terminal box. When
applicable, install conduit using local and national
electrical codes which apply to the application.
3. The instrument is not polarity sensitive. Connect
one wire from the control system output card to one of
2
Содержание FIELDVUE DVC6200f
Страница 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Страница 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Страница 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Страница 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Страница 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Страница 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Страница 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Страница 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Страница 251: ...Principle of Operation November 2010 239 A A Appendix A Principle of Operation Digital Valve Controller Operation 240 A ...
Страница 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Страница 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Страница 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Страница 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Страница 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Страница 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...
Страница 325: ...This page intentionally left blank ...