Basic Setup
BASIC_SETUP
42
Actuator Style
ACTUATOR_STYLE
42.1
RW
MAN
OOS
1=Spring & Diaphragm
2=Piston-Dbl w/o Spring
3=Piston-Dbl w/Spring
4=Piston Sgl w/Spring
1=Spring &
Diaphragm
SETUP
Data Type: Enum (Uint8)
Zero Power Condition
ZERO_PWR_COND
42.2
RW
MAN
OOS
1=Valve Closed
2=Valve Open
1=Valve Closed
SETUP
Data Type: (Uint8)
Enum Identifies whether the valve
is open or closed when instrument
power is lost.
Travel Sensor Motion
TRAVEL_SEN_MOTION
42.3
RW
MAN
OOS
1=Counter Clockwise
2=Clockwise
1=Counter
Clockwise
SETUP
Data Type: Enum (Uint8)
Feedback Connection
FEEDBACK_CONN
42.4
RW
MAN
OOS
100: Default Array
64: SStem #19 Array
65: SStem #25 Array
66: SStem #38 Array
67: SStem #50 Array
70: SStem #100 Array
74: SStem #200 Array
85: SStem #1 Roller
Array
90: RShaft End Array
95: RShaft #1 Window
Array
97: RShaft #2 Window
Array
SETUP
Data Type: Enum (Uint8)
Relay Type
RELAY_TYPE
42.5
RW
MAN
OOS
1=Relay A or C--Double
or Single Direct
2=Relay B--Single
Reverse
5=Relay C-Special App.
--Single Direct
6=Relay B-Special App.
--Single Reverse
9=Lo-Bleed Relay A or
C--Double or Single
Direct
10=Lo-Bleed Relay B--
Single Reverse
13=Lo-Bleed Relay
C-Special App.--Single
Direct
10=Lo-Bleed Relay
B-Special App.-
−
Single
Reverse
=Relay A or
C--Double or
Single Direct
SETUP
Data Type: Enum (Uint8)
Maximum Supply Pressure
MAX_SUPP_PRESS
42.6
RW
MAN
OOS
>
0, < = 150
35 psig
SETUP
Data Type: Float
Pressure Range Hi
PRESS_RANGE_HI
42.7
RW
MAN
OOS
>
0, < = 150
15.0 psig
SETUP
Data Type: Float
Defines pressure corresponding to
max pressure in pressure control
mode.
Pressure Range Lo
PRESS_RANGE_LO
42.8
RW
MAN
OOS
>
= 0, < = 150
3.0 psig
SETUP
Data Type: Float
Defines pressure corresponding to
minimum pressure in pressure
control mode.
Travel Calibration Trigger
TVL_CAL_TRIGGER
42.9
RW
MAN
OOS
1 = Aux Term ignored
1
SETUP
Not available in the DVC6200f
Travel Tuning Set
TVL_TUNING_SET
42.10
RW
MAN
OOS
1=B, 2= C, ...12=M
23=X
2=C
SETUP
Data Type: Enum (Uint8)
Letter (B through M or X)
Pressure Tuning Set
PRESS_TUNING_SET
42.11
RW
MAN
OOS
1=B, 2=C, ...12= M
23=X
2=C
SETUP
Data Type: Enum (Uint8)
Letter (B through M or X)
−
Continued
−
4
Содержание FIELDVUE DVC6200f
Страница 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Страница 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Страница 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Страница 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Страница 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Страница 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Страница 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Страница 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Страница 251: ...Principle of Operation November 2010 239 A A Appendix A Principle of Operation Digital Valve Controller Operation 240 A ...
Страница 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Страница 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Страница 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Страница 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Страница 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Страница 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...
Страница 325: ...This page intentionally left blank ...