DVC6200f Digital Valve Controller
November 2010
112
B2720 / IL
BKCAL
OUT
OUT
CAS
IN
PID
BKCAL
IN
FF
VAL
IN
TRK
IN
D
TRK
VAL
BKCAL_IN
=
THE ANALOG INPUT VALUE AND STATUS FROM ANOTHER
BLOCK’S BKCAL _OUT OUTPUT THAT IS USED FOR
BACKWARD OUTPUT TRACKING FOR BUMPLESS TRANSFER
AND TO PASS LIMIT STATUS.
CAS_IN
=
THE REMOTE SETPOINT VALUE FROM ANOTHER FUNCTION
BLOCK.
FF_VAL
=
THE FEEDFORWARD CONTROL INPUT VALUE AND STATUS.
IN
=
THE CONNECTION FOR THE PROCESS VARIABLEFROM
ANOTHER FUNCTION BLOCK.
TRK_IN_D
=
INITIATES THE EXTERNAL TRACKING FUNCTION.
TRK_VAL
=
THE VALUE AFTER SCALING APPLIED TO OUT IN LOCAL
OVERRIDE MODE.
BKCAL_OUT
=
THE VALUE AND STATUS REQUIRED BY THE BKCAL_IN INPUT
OF ANOTHER FUNCTION BLOCK TO PREVENT RESET WINDUP
AND TO PROVIDE BUMPLESS TRANSFER TO CLOSED LOOP
CONTROL.
OUT
=
THE BLOCK OUTPUT AND STATUS.
Figure 4-9. PropoIDerivative (PID) Function Block
PID Function Block Overview
The PID function block combines all of the necessary
logic to perform proportional/integral/derivative (PID)
control. The block supports mode control, signal
scaling and limiting, feedforward control, override
tracking, alarm limit detection, and signal status
propagation.
The block supports two forms of the PID equation:
Standard and Series. You can choose the appropriate
equation using the MATHFORM [70] parameter. The
Standard ISA PID equation is the default selection.
Standard Out
+
GAIN
ex
ǒ
1
)
1
t
r
s
)
1
)
t
d
s
T
t
d
s
)
1
Ǔ
)
F
Series Out
+
GAIN
ex
ǒ
1
)
1
t
r
s
Ǔ
)
ǒ
t
d
s
)
1
T
t
d
s
)
1
Ǔ
)
F
where
GAIN: proportional gain value
τ
r
:
integral action time constant (RESET
parameter) in seconds
s:
laplace operator
τ
d
:
derivative action time constant (RATE
parameter)
α
:
fixed smoothing factor of 0.1 applied to
RATE
F:
feedforward control contribution from the
feedforward input (FF_VAL)
E:
error between setpoint and process variable
To further customize the block for use in your
application, you can configure filtering, feedforward
inputs, tracking inputs, setpoint and output limiting,
PID equation structures, and block output action.
Table 4-32 lists the PID block parameters and their
descriptions, units of measure, and index numbers,
and figure 4-10 illustrates the internal components of
the PID function block.
Modes
The PID function block supports the following modes:
Manual (Man)—The block output (OUT [9]) may
be set manually.
Automatic (Auto)—The SP [8] may be set
manually and the block algorithm calculates OUT [9].
Cascade (Cas)—The SP [8] is calculated in
another block and is provided to the PID block through
the CAS_IN [18] connection.
RemoteCascade (RCas)—The SP [8] is
provided by a host computer that writes to the
RCAS_IN [32] parameter.
RemoteOutput (ROut)—The OUT [9] is provided
by a host computer that writes to the ROUT_IN [33]
parameter.
Local Override (LO)—The track function is
active. OUT [9] is set by TRK_VAL [39]. The
BLOCK_ERR [6] parameter shows Local override.
Initialization Manual (IMan)—The output path
is not complete (for example, the cascade
−
to
−
slave
path might not be open). In IMan mode, OUT [9]
tracks BKCAL_IN [27].
Out of Service (OOS)—The block is not
processed. The OUT [9] status is set to Bad: Out of
Service. The BLOCK_ERR [6] parameter shows Out
of service.
4
Содержание FIELDVUE DVC6200f
Страница 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Страница 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Страница 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Страница 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Страница 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Страница 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Страница 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Страница 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Страница 251: ...Principle of Operation November 2010 239 A A Appendix A Principle of Operation Digital Valve Controller Operation 240 A ...
Страница 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Страница 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Страница 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Страница 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Страница 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Страница 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...
Страница 325: ...This page intentionally left blank ...