AI Function Block
November 2010
161
Indirect
Indirect signal conversion converts the signal linearly
to the accessed channel input value (or the simulated
value when simulation is enabled) from its specified
range (XD_SCALE [10]) to the range and units of the
PV [7] and OUT [8] parameters (OUT_SCALE [11]).
X (EU **@100%
−
EU **@0%) + EU **@0%
**OUT_SCALE values
PV =
100
(
)
FIELD_VAL
Indirect Square Root
Indirect Square Root signal conversion takes the
square root of the value computed with the indirect
signal conversion and scales it to the range and units
of the PV [7] and OUT [8] parameters.
PV =
FIELD_VAL
X (EU **@100%
−
EU **@0%) + EU **@0%
100
)
(
**OUT_SCALE values
When the converted input value is below the limit
specified by the LOW_CUT [17] parameter, a value of
zero is used for the converted value (PV [7]). This
option is useful to eliminate false readings when the
differential pressure measurement is close to zero.
Note
Invert is the only I/O option supported
by the AI block. You can set the I/O
option in Out of Service mode only.
Advanced Features
The AI function block provided with the DVC6200f
provides added capability through the addition of the
following parameters:
ALARM_SEL—Allows one or more of the process
alarm conditions detected by the AI function block to
be used in setting its OUT_D [37] parameter.
OUT_D—Discrete output of the AI function block
based on the detection of process alarm condition(s).
This parameter may be linked to other function blocks
that require a discrete input based on the detected
alarm condition.
STDDEV and CAP_STDDEV— are diagnostic
parameters that can be used to determine the
variability of the process.
Simulation
To support testing, you can either change the mode of
the block to manual and adjust the output value, or
you can enable simulation through the configuration
tool and manually enter a value for the measurement
value and its status. To enable simulation, you must
first install the Simulate Enable jumper across the
instrument AUX terminals (see page 213). Next you
must use the configuration tool to enable the
parameter SIMULATE [9].
With simulation enabled, the actual measurement
value has no impact on the OUT [8] value or the
status.
Block Errors
Table 4-55 lists conditions reported in the
BLOCK_ERR [6] parameter. Conditions in italics are
inactive for the AI block and are given here only for
your reference.
Table 4-55. BLOCK_ERR Conditions
Condition
Number
Condition Name and Description
0
Other
1
Block Configuration Error - the selected channel carries
a measurement that is incompatible with the engineering
units selected in XD_SCALE, the L_TYPE parameter is
not configured, or CHANNEL = zero.
2
Link Configuration Error
3
Simulate Active - Simulation is enabled and the block is
using a simulated value in its execution.
4
Local Override
5
Device Fault State
6
Device Needs Maintenance Soon
7
Input failure/process variable had Bad status - The
hardware is bad, or a bad status is being simulated
8
Output failure
9
Memory failure
10
Lost Static Data
11
Lost NV Data
12
Readback Check Failed
13
Device Needs Maintenance Now
14
Power Up
−
This condition exists until the AI function
block executes for the first time.
15
Out of Service - The actual mode is Out of Service.
4
Содержание FIELDVUE DVC6200f
Страница 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Страница 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Страница 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Страница 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Страница 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Страница 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Страница 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Страница 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Страница 251: ...Principle of Operation November 2010 239 A A Appendix A Principle of Operation Digital Valve Controller Operation 240 A ...
Страница 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Страница 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Страница 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Страница 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Страница 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Страница 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...
Страница 325: ...This page intentionally left blank ...