DVC6200f Digital Valve Controller
November 2010
172
MAI Function Block Parameter List
Read/Write Capability: RO
−
Read Only, RW
−
Read Write
Mode: The block mode(s) required to write to the parameter
Double indentation and shaded Index Number indicates sub-parameter
Table 4-64. MAI Function Block Parameter Definitions
Label
Parameter Name
Index
Number
RO /
RW
Mode
Range
Initial Value
Description
Static Revision
ST_REV
1
RO
N/A
0 to 65535
0
Data Type: Unsigned16
The revision level of the static data
associated with the input selector block.
The revision value will be incremented
each time a static parameter value in the
block is changed.
Tag Description
TAG_DESC
2
7 bit ASCII
spaces
Data Type: Octet String
The user description of the intended
application of the block.
Strategy
STRATEGY
3
0 to 65535
0
Data Type: Unsigned16
The strategy field can be used to identify
grouping of blocks. This data is not
checked or processed by the block.
Alert Key
ALERT_KEY
4
1 to 255
0
Data Type: Unsigned8
The identification number of the plant
unit. This information may be used in the
host for sorting alarms, etc.
Block Mode
MODE_BLK
5
Data Type: DS-69
The actual, target, permitted, and normal
modes of the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal:
Most
common
mode
for Target
TARGET
5.1
RW
ALL
OOS, MAN, AUTO
OOS
ACTUAL
5.2
RO
ALL
OOS
PERMITTED
5.3
RW
ALL
OOS+MAN+AUTO
OOS, MAN, AUTO
NORMAL
5.4
RW
ALL
AUTO
AUTO
Block Error
BLOCK_ERR
6
RO
1: Block Configuration
Error
7: Input Failure/ Bad PV
Status
14: Power-up
15: Out-of-Service
Data Type: Bit String
0 = Inactive
1 = Active
This parameter reflects the error status
associated with the hardware or software
components associated with a block. It is
a bit string, so that multiple errors may
be shown.
MAI Channel
CHANNEL
7
21 only
0 = undefined
This variable must be set to 21. Channel
assignments to the 8 outputs is done
through MAI_CHANNEL_MAP
parameter in transducer block.
1=FINAL_VALUE
2=TRAVEL_TARGET
3=FINAL_POSITION_VALUE
4=TRAVEL
5=SUPPLY_PRESS
6=ACT_PRESS_A
7=ACT_PRESS_B
8=ACT_PRESS_DIFF
9=DRIVE_SIGNAL
10=TRAVEL_DEVIATION
11=TEMPERATURE
12=CYCLE_COUNT
13=TRAVEL_ACCUM
Output 1
OUT_1
8
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.FINAL_VALUE
Data Type: DS-65
The block output value and status.
Output 2
OUT_2
9
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.TRAVEL_TARGET
Data Type: DS-65
The block output value and status.
Output 3
OUT_3
10
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.FINAL_POSITION_
VALUE
Data Type: DS-65
The block output value and status.
−
Continued
−
4
Содержание FIELDVUE DVC6200f
Страница 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Страница 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Страница 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Страница 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Страница 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Страница 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Страница 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Страница 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Страница 251: ...Principle of Operation November 2010 239 A A Appendix A Principle of Operation Digital Valve Controller Operation 240 A ...
Страница 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Страница 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Страница 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Страница 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Страница 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Страница 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...
Страница 325: ...This page intentionally left blank ...