Emerson FB3000 RTU Instruction Manual
D301851X012
May 2022
70
Service and Troubleshooting
5.4
Removing/Replacing the SRAM Batteries
A 3V lithium coin cell battery in each of the two power supply modules provides backup
power for the SRAM and the real time clock. These batteries operate continuously with a
typical expected cumulative operation of 4900 hours if only one power module is
installed, or 9800 hours if both power modules are installed.
A separate third lithium coin cell battery in the CPU module provides backup power for
SRAM and the real time clock only when the CPU module is physically removed from the
RTU, or if both power supply modules are physically removed from the RTU. The typical
expected cumulative operation for this third backup battery is 1250 hours.
You do not need to power down the unit to replace the SRAM backup batteries.
Important
If the unit is ever powered down without the SRAM batteries installed, SRAM data is lost;
this may include configuration data, alarms, events, and history. Always back up your
data before you remove the SRAM batteries if you know that main power will also be off.
Important
Replacement SRAM backup battery for the CPU module must be RENATA CR1632.
Important
Replacement SRAM backup batteries for the power module(s) must be one of the
following:
RENATA CR2450HT
MAXELL CR2450HR
PANASONIC BR2450A
MURATA CR2450W
DANGER
Ensure the RTU is in a non-hazardous area. Never open the enclosure in a hazardous
area.
DANGER
EXPLOSION HAZARD: Do not disconnect equipment unless power has been removed
or the area is known to be non-hazardous.
DANGER
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class
I, Division 2.
Содержание FB3000
Страница 7: ...FB3000 CSA Approval Information CD9411L Issued March 11 2021 CSA 5 ...
Страница 8: ......
Страница 12: ......
Страница 46: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 34 Installation ...
Страница 68: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 56 I O Configuration and Wiring ...
Страница 72: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 60 Operation ...
Страница 94: ......