I/O Configuration and Wiring
The actual values read back are unavailable to the user and these checks are made
internal to the firmware.
3.3
Digital Inputs
The FB3000 RTU supports a mixed I/O module which includes eight channels you can
individually configure as either analog inputs (AI), digital inputs (DI) or pulse inputs (PI).
The number of mixed I/O modules supported depends on the number of I/O slots in the
RTU.
When configured as digital inputs, the channels have the following characteristics:
Table 3-4: Digital input Characteristics
Type
Number Supported Characteristics
Digital Input
(DI)
Any of AIDIPI_01
through AIDIPI_08
can be individually
configured as digital
inputs.
When a channel is configured as a DI it cannot be
used as an AI or PI channel
The range of digital inputs must remain within the
span of 0VDC to 30VDC.
All digital inputs have 1V hysteresis applied to
them; switching levels are 2VDC for rising signals
and 1VDC for falling signals.
Dry Contact
Digital inputs require an internal or external pull-up
to 30VDC and pull-downs must be to ISO_GND.
When using internal pull-ups or pull-downs, you
have a choice of 2mA or 66µA (selectable in
FBxConnect) or a 66µA or 2mA pull-down to
ISO_GND. Choice of higher current (2mA) results in
faster input; choice of lower current (66µA) results
in slower input.
10 Hz filter (low speed)
Содержание FB3000
Страница 7: ...FB3000 CSA Approval Information CD9411L Issued March 11 2021 CSA 5 ...
Страница 8: ......
Страница 12: ......
Страница 46: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 34 Installation ...
Страница 68: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 56 I O Configuration and Wiring ...
Страница 72: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 60 Operation ...
Страница 94: ......